⭐ 欢迎来到虫虫下载站! | 📦 资源下载 📁 资源专辑 ℹ️ 关于我们
⭐ 虫虫下载站

📄 53569

📁 神经网络昆斯林的新闻组分类2006
💻
📖 第 1 页 / 共 5 页
字号:
	When you install a GFCI, it's a good idea to use the little	"ground fault protected" stickers that come with it and mark	the outlets downstream of the GFCI.  You can figure out which	outlets are "downstream", simply by tripping the GFCI with the	test button and see which outlets are dead.Subject: What's the purpose of the ground prong on an outlet, then?	Apart from their use in electronics, which we won't comment on,	and for certain fluorescent lights (they won't turn on without	a good ground connection), they're intended to guard against	insulation failures within the device.  Generally, the case of	the appliance is connected to the ground lead.  If there's an	insulation failure that shorts the hot lead to the case, the	ground lead conducts the electricity away safely (and possibly	trips the circuit breaker in the process).  If the case is not	grounded and such a short occurs, the case is live -- and if	you touch it while you're grounded, you'll get zapped.  Of	course, if the circuit is GFCI-protected, it will be a very	tiny zap -- which is why you can use GFCIs to replace	ungrounded outlets (both NEC and CEC).	There are some appliances that should *never* be grounded.  In	particular, that applies to toasters and anything else with	exposed conductors.  Consider:  if you touch the heating	electrode in a toaster, and you're not grounded, nothing will	happen.  If you're slightly grounded, you'll get a small shock;	the resistance will be too high.  But if the case were	grounded, and you were holding it, you'd be the perfect path to	ground...Subject: Why is one prong wider than the other?  Polarization	Nowadays, many two-prong devices have one prong wider than the	other.  This is so that the device could rely (not guaranteed!)	on one specific wire being neutral, and the other hot.	This is particularly advantageous in light fixtures, where the	the shell should neutral (safety), or other devices which want to	have an approximate ground reference (ie: some radios).	Most 2-prong extension cords have wide prongs too.	This requires that you wire your outlets and plugs the right	way around.  You want the wide prong to be neutral, and the	narrow one hot.  Most outlets have a darker metal for the	hot screw, and lighter coloured screw for the neutral.	If not, you can usually figure out which is which by which	prong the terminating screw connects to.Subject: What kind of outlets do I need in a kitchen?	The NEC requires at least two 20 amp ``small appliance	circuits'' for kitchens.  The CEC requires split-duplex	receptacles.  Outlets must be installed such that no point is more	than 24" (NEC) (900 mm CEC) from an outlet.  Every counter wider	than 12" (NEC) or 300 mm (CEC) must have at least one outlet.	The circuit these outlets are on may not feed any outlets except	in the kitchen, pantry, or dining room.  Furthermore, these circuits	are in addition to any required for refrigerators, stoves, microwaves,	lighting, etc.  Non-dedicated outlets within 6' of a sink *must* be	protected by a GFCI (NEC only).	Split duplex receptacles are fed with a 220V circuit.  The tab	is broken on the hot side of the outlet, and one hot goes to	the upper outlet, and the other hot goes to the lower outlet.	The neutral connects to both outlets through one screw.  When	"carrying through" to another outlet, the neutral must be	pigtailed, such that removing the outlet, or having the neutral	connection fall off doesn't cause the neutral to disconnect	from downstream outlets.Subject: Where must outlets and switches be in bathrooms?	There must be at least one outlet in each bathroom, adjacent to	the sink, in addition to any outlet that may be incorporated in	the light fixture.  All such outlets *must* be GFCI-protected.Subject: What is Romex/NM/NMD?  What is BX?  When should I use each?	Romex is a brand name for a type of plastic insulated wire.	Sometimes called non-metallic sheath.  The formal name is NM.	This is suitable for use in dry, protected areas (ie: inside	stud walls, on the sides of joists etc.), that are not subject	to mechanical damage or excessive heat.  Most newer homes are	wired almost exclusively with NM wire.  There are several	different categories of NM cable.	BX cable -- technically known as armored cable or "AC" has a	flexible aluminum or steel sheath over the conductors and is	fairly resistant to damage.	TECK cable is AC with an additional external thermoplastic	sheath.		Protection for cable in concealed locations: where NM or AC cable	is run through studs, joists or similar wooden members, the outer	surface of the cable must be kept at least 32mm/1.25" (CEC & NEC)	from the edges of the wooden members, or the cable should be protected	from mechanical injury.  This latter protection can take the form of	metal plates (such as spare outlet box ends) or conduit.	[Note: inspector-permitted practise in Canada suggests that armored	cable, or flexible conduit can be used as the mechanical protection,	but this is technically illegal.]	Additional protection recommendations (these are rules in the	Canadian codes - they are reasonable answers to the vague	references to "exposed to mechanical damage" in both the NEC	and CEC):	    - NM cable should be protected against mechanical damage	      where it passes through floors or on the surface of walls	      in exposed locations under 5 feet from the floor.	      Ie: use AC instead, flexible conduit, wooden guards etc.	    - Where cable is suspended, as in, connections to furnaces	      or water heaters, the wire should be protected.  Canadian	      practise is usually to install a junction or outlet	      box on the wall, and use a short length of AC cable	      or NM cable in flexible conduit to "jump" to the appliance.	      Stapling NM to a piece of lumber is also sometimes used.	    - Where NM cable is run in close proximity to heating	      ducts or pipe, heat transfer should be minimized by	      means of a 25mm/1" air space, or suitable insulation	      material (a wad of fiberglass).	    - NM cable shall be supported within 300mm/1' of every box	      or fitting, and at intervals of no more than 1.5m/5'.	      Holes in joists or studs are considered "supports".	      Some slack in the cable should be provided adjacent to	      each box.  [while fishing cable is technically in violation,	      it is permitted where "proper" support is impractical]	    - 2 conductor NM cable should never be stapled on edge.	      [Knight also insists on only one cable per staple, referring	      to the "workmanship" clause, but this seems more honoured	      in the breach...]	    - cable should never be buried in plaster, cement or	      similar finish.	    - cable should be protected where it runs behind baseboards.	    - Cable may not be run on the upper edge of ceiling joists	      or the lower edges of rafters where the headroom is more	      than 1m (39").	Whenever BX cable is terminated at a box with a clamp, small	plastic bushings must be inserted in the end of the cable to	prevent the clamps forcing the sharp ends of the armor through	the insulation.	BX is sometimes a good idea in a work shop unless covered by	solid wall coverings.	In places where damage is more likely (like on the back wall of	a garage ;-), you may be required to use conduit, a	UL- (or CSA-) approved metal pipe.  You use various types of	fittings to join the pipe or provide entrance/exit for the	wire.	Service entrances frequently use a plastic conduit.	In damp places (eg: buried wiring to outdoor lighting) you will	need special wire (eg: CEC NMW90, NEC UF).  NMW90 looks like	very heavy-duty NMD90.  You will usually need short lengths of	conduit where the wire enters/exits the ground.  [See underground	wiring section.] 	Thermoplastic sheath wire (such as NM, NMW etc.) should not be 	exposed to direct sunlight unless explicitly approved for that 	purpose.	Many electrical codes do not permit the routing of wire through	furnace ducts, including cold air return plenums constructed	by metal sheeting enclosing joist spaces.   The reason for this	is that if there's a fire, the ducting will spread toxic gasses	from burning insulation very rapidly through the building.	Teflon insulated wire is permitted in plenums in many areas.	 	Canada appears to use similar wire designations to the US, 	except that Canadian wire designations usually include the 	temperature rating in Celsius.  Eg: "AC90" versus "AC".	In the US, NM-B is 90 degrees celcius.	NOTE: local codes vary.  This is one of the items that changes	most often.  Eg: Chicago codes require conduit *everywhere*.	There are very different requirements for mobile homes.	Check your local codes, *especially* if you're doing anything	that's the slightest out of the ordinary.	Wire selection table (incomplete - the real tables are enormous,	uncommon wire types or applications omitted)	Condition			Type	CEC	NEC	Exposed/Concealed dry		plastic	NMD90	NM					armor	AC90	AC						TECK90	Exposed/Concealed damp		plastic	NMD90	NMC					armor	ACWU90						TECK90	Exposed/Concealed wet		plastic	NMWU90					armor	ACWU90						TECK90		Exposed to weather		plastic	NMWU						TW etc.					armor	TECK90		Direct earth burial/		plastic	NMWU*	UF	Service entrance			RWU						TWU					armor	RA90						TECK90						ACWU90	[* NMWU not for service entrance]Subject: Should I use plastic or metal boxes?	The NEC permits use of plastic boxes with non-metallic cable	only.  The reasoning is simple -- with armored cable, the box	itself provides ground conductor continuity.  U.S. plastic	boxes don't use metal cable clamps.	The CEC is slightly different.  The CEC never permits cable	armor as a grounding conductor.  However, you must still	provide ground continuity for metallic sheath.  The CEC also	requires grounding of any metal cable clamps on plastic boxes.	The advantage of plastic boxes is comparatively minor even for	non-metallic sheathed cable -- you can avoid making one ground	connection and they sometimes cost a little less.  On the other	hand, plastic boxes are more vulnerable to impacts.  For	exposed or shop wiring, metal boxes are probably better.Subject: Junction box positioning?	A junction box is a box used only for connecting wires together.	Junction boxes must be located in such a way that they're accessible	later.  Ie: not buried under plaster.  Excessive use of junction	boxes is often a sign of sloppy installation, and inspectors may	get nasty.Subject: Can I install a replacement light fixture?	In general, one can replace fixtures freely, subject to a few	caveats.  First, of course, one should check the amperage	rating of the circuit.  If your heart is set on installing half	a dozen 500 watt floodlights, you may need to run a new wire	back to the panel box.  But there are some more subtle	constraints as well.  For example, older house	wiring doesn't have high-temperature insulation.  The excess	heat generated by a ceiling-mounted lamp can and will cause the	insulation to deteriorate and crack, with obvious bad results.	Some newer fixtures are specifically marked for high	temperature wire only.  (You may find, in fact, that your	ceiling wiring already has this problem, in which case	replacing any devices is a real adventure.)	Other concerns include providing a suitable ground for some	fluorescent fixtures, and making sure that the ceiling box and	its mounting are strong enough to support the weight of a heavy	chandelier or ceiling fan.  You may need to install a new box	specifically listed for this purpose.  A 2x4 across the ceiling	joists makes a good support.  Metal brackets are also available	that can be fished into ceilings thru the junction box hole and	mounted between the joists.	There are special rules for recessed light fixtures such as	"pot" lamps or heat lamps.  When these are installed in insulated	ceilings, they can present a very substantial fire hazard.	The CEC provides for the installation of pot lamps in insulated	ceilings, provided that the fixture is boxed in a "coffin" (usually	8'x16"x12" - made by making a pair of joists 12" high, and covering	with plywood) that doesn't have any insulation.  (Yes, that's 8 *feet*	long)	NEC rules are somewhat less stringent.  They require at least 3"	clearance between the fixture and any sort of thermal insulation.	The rules also say that one should not obstruct free air movement,	which means that a CEC-style ``coffin'' might be worthwhile.	Presumably, that's up to the local inspector.  [The CEC doesn't	actually mandate the coffin per-se, this seems to be an inspector	requirement to make absolutely certain that the fixture can't get

⌨️ 快捷键说明

复制代码 Ctrl + C
搜索代码 Ctrl + F
全屏模式 F11
切换主题 Ctrl + Shift + D
显示快捷键 ?
增大字号 Ctrl + =
减小字号 Ctrl + -