📄 siem8052.gsg
字号:
;========================================================
; GSD-File for DP/PA-Link IM157 Siemens AG
; MLFB : 6ES7 157-0AA81-0XA0
; MLFB : 6ES7 157-0AA80-0XA0
; MLFB : 6ES7 157-0AA00-0XA0
;
; Date : 14.02.03 V1.6 GW
; File : "SIEM8052.GSG"
; Support : Customer-Support Nuernberg ++ (0)911/895/7000
;========================================================
;
#Profibus_DP
; Prm-Text-Definition-List:
PrmText=1
Text(0)="sperren"
Text(1)="freigeben"
EndPrmText
;
PrmText=2
Text(160)="160 Byte Gesamtdiagnose"
Text(98)="98 Byte Standard+Kennung+Modul"
Text(36)="36 Byte Standard+Kennung"
Text(6)="6 Byte Standarddiagnose"
EndPrmText
;
; Ext-User-Prm-Data-Definition-List:
ExtUserPrmData=1 "Anlauf bei Soll- <> Istausbau"
Bit(0) 1 0-1
Prm_Text_Ref=1
EndExtUserPrmData
;
ExtUserPrmData=2 "Diagnoselaenge"
Unsigned8 160 6,36,98,160
Prm_Text_Ref=2
EndExtUserPrmdata
;
; Unit-Definition-List:
GSD_Revision = 2
Vendor_Name = "SIEMENS"
Model_Name = "DP/PA-Link (IM157)"
Revision = "V1.6"
Ident_Number = 0x8052
Protocol_Ident = 0
Station_Type = 0
Hardware_Release = "V2.2"
Software_Release = "V3.5"
9.6_supp = 1
19.2_supp = 1
45.45_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_45.45 = 250
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Repeater_Ctrl_Sig = 2
;
Implementation_Type = "ASPC2"
Bitmap_Device = "IM157_1N"
Bitmap_SF = "IM157_1S"
;
; Slave-Specification:
OrderNumber = "6ES7 157-0AA**-0XA0"
Freeze_Mode_supp = 0
Sync_Mode_supp = 0
Auto_Baud_supp = 1
Set_Slave_Add_supp = 0
Fail_Safe = 1
Min_Slave_Intervall = 10
Modular_Station = 1
Max_Module = 223
Max_Input_Len = 244
Max_Output_Len = 244
Max_Data_Len = 488
Max_Diag_Data_Len = 160
Slave_Family = 9@PA
;
; UserPrmData: Length and Preset
User_Prm_Data_Len = 11
User_Prm_Data = 0x00,0x01,0x00,0x08,0x81,0x00,0x00,0xa0,0x00,0x80,0x52
Max_User_Prm_Data_Len=11
Ext_User_Prm_Data_Const(0) = 0x00,0x01,0x00,0x08,0x81,0x00,0x00,0xa0,0x00,0x80,0x52
Ext_User_Prm_Data_Ref(1)=1
Ext_User_Prm_Data_Ref(7)=2
;
; Publisher_Supp = 1
;
;
; Module-Definitions:
;==============================================================
; reserved Module_References:
;
; komplexer PA-Slave : 1
; Ende komplexer PA-Slave : 2
; Leer-Slot : 3
;
; PA-Adresse nicht benutzt : 5
;
; SIEMENS SITRANS P : 20 - 29 ID 80B4
; SIEMENS SITRANS T3K Temp. : 30 - 39 ID 8090
; SIEMENS SIPART PS2 : 40 - 49 ID 8079
; SIEMENS SITRANS F : 50 - 69 ID 8091
; E+H Cerabar S : 70 - 79 ID 1501
; E+H Prosonic T : 80 - 89 ID 1502
; E+H Deltapilot S : 90 - 99 ID 1503
; E+H Deltabar S : 100 - 109 ID 1504
; E+H TMD834 : 110 - 119 ID 1507
; E+H Micropilot II : 120 - 129 ID 150A
; E+H MYCOM CPM : 130 - 139 ID 1508
; E+H MYCOM CLM-ID : 140 - 149 ID 1509
; E+H MYCOM CLM-CD : 150 - 159 ID 150B
; E+H Promag 33,35 : 160 - 169 ID 1505
; E+H Promass 63 : 170 - 189 ID 1506
; E+H Prowirl 77 : 190 - 199 ID 1510
; E+H Smartec S CLD132 : 200 - 209 ID 151B
; BUERKERT 8642 : 210 - 229
; KROHNE IFC 090/IFC 090 i : 230 - 239 ID F401
; KROHNE MFC081/085 : 240 - 249 ID F701
; SAMSON Positioner 3785 : 250 - 269
; SMAR FY303/FP303/FI303 : 270 - 289 ID 0897, 0898, 0899
; KROHNE BM 70 A/P ; 290 - 299 ID F901
; E+H MYPRO CLM/CLD 431 : 300 - 309 ID 150C
; E+H MYPRO CPM 431 : 310 - 319 ID 150D
; E+H MYCOM CLM152 : 320 - 329 ID 1513
; E+H FXA 164 : 330 - 339 ID 1514
; E+H Liquisys S CLM2x3 : 340 - 349 ID 1515
; E+H Liquisys S CPM2x3 : 350 - 359 ID 1516
; E+H Liquisys S CUM2x3 : 360 - 369 ID 1517
; E+H Liquisys S COM2x3 : 370 - 379 ID 1518
; E+H Liquisys S CCM2x3 : 380 - 389 ID 1519
; E+H Cerabar M : 390 - 399 ID 151C
; KROHNE BM100A : 400 - 409
; KROHNE H 250 ESK-3 PA : 410 - 419
; E+H Cerabar S, 2nd Gener. : 420 - 429 ID 1501
; E+H Prosonic T, 2nd Gener. : 430 - 439 ID 1502
; E+H Deltapilot S, 2nd Gener. : 440 - 449 ID 1503
; E+H Deltabar S, 2nd Gener. : 450 - 459 ID 1504
; SIEMENS SIPAN 32 : 460 - 469 ID 809D
; SIEMENS OXYMAT / ULTRAMAT : 470 - 479 ID 809C
; E+H Micropilot M : 480 - 489 ID 1522
; E+H TMT184 : 490 - 499 ID 1523
; E+H Promag 50 : 500 - 509 ID 1525
; E+H Promag 53 : 510 - 519 ID 1527
; BUERKERT 8630 : 520 - 539 ID C630
; SIEMENS SITRANS LR : 540 - 549 ID 80B2
; SIEMENS SITRANS FM : 550 - 559 ID 80C4
; E+H PROMASS 80/83 PA : 560 - 569 ID 1528, 152A
; METSO Automation ND800PA : 570 - 589 ID 052D
; VEGA VEGAPULS 40/50 : 590 - 600 ID 0492
; VEGA VEGASON 50 : 600 - 609 ID 0493
; VEGA VEGAFLEX 50 : 610 - 619 ID 0494
; VEGA VEGABAR : 620 - 629 ID 0495
; VEGA VEGACAP : 630 - 639 ID 0496
; VEGA D90 Series : 640 - 649 ID 0497
; SIEMENS SITRANS P DSIII : 650 - 659 ID 80A6
; E+H Prosonic M : 660 - 669 ID 152C
; E+H Levelflex M : 670 - 679 ID 152D
; E+H PROSONIC FLOW 90/93 PA : 680 - 689 ID 152F, 1530
; E+H Liquiphant M/S : 690 - 699 ID 152B
; Micro Motion MVD 2000 PA : 700 - 709 ID 057A
; E+H MYCOM CLM153cd/id PA : 710 - 719 ID 1535, 1537
; E+H MYCOM CPM153 PA : 720 - 729 ID 1539
; Danfoss A/S MASS 6000 : 730 - 749 ID 0507
; PA Flow,dens,temp 3AI,1TOT : 750 - 759 ID 9742
; BUERKERT 8635 : 760 - 769 ID 0569
; SMAR LD303/IF303/TP303 : 770 - 779 ID 0895, 0896, 0904
; SMAR TT303 : 780 - 789 ID 089A
; SMAR LD293 : 790 - 799 ID 0906
; Danfoss MASS6000 PA Extended : 800 - 819 ID 0648
; Danfoss MAG6000 PA Extended : 820 - 829 ID 0649
; Danfoss MAG6000 PA : 830 - 839 ID 0506
; Rosemount Temp. Transmitter : 840 - 849 ID 3244
; Rosemount Press. Transmitter : 850 - 859 ID 3051
;
;=================PA-Adresse nicht benutzt=====================
Module = "PA-Adresse nicht benutzt" 0x01,0xfe
5
EndModule
;=================Firmenspezifische GSDs=======================
Module = "SIEMENS SITRANS P" 0x94
20
EndModule
;==============================================================
Module = "SIEMENS SITRANS T3K Temp." 0x94
30
EndModule
;==============================================================
Module = "SIEMENS SIPART PS2 Beginn" 0x01,0xfc
40
EndModule
Module = "== SP," 0x82,0x84,0x08,0x05
41
EndModule
Module = "== READBACK + POS_D, SP" 0xC6,0x84,0x86,0x08,0x05,0x08,0x05,0x05,0x05
42
EndModule
Module = "== CHECKBACK, SP" 0xC3,0x84,0x82,0x08,0x05,0x0A
43
EndModule
Module = "== READBACK+POS_D+CHECKBACK, SP" 0xC7,0x84,0x89,0x08,0x05,0x08,0x05,0x05,0x05,0x0A
44
EndModule
Module = "== RC_OUT, RC_IN" 0xC4,0x84,0x84,0x08,0x05,0x08,0x05
45
EndModule
Module = "== RC_OUT + CHECKBACK, RC_IN" 0xC5,0x84,0x87,0x08,0x05,0x08,0x05,0x0A
46
EndModule
Module = "== RB+RC_OUT+POS_D+CB, SP+RC_IN" 0xCB,0x89,0x8E,0x08,0x05,0x08,0x05,0x08,0x05,0x08,0x05,0x05,0x05,0x0A
47
EndModule
Module = "SIEMENS SIPART PS2 Ende" 0x01,0xfd
48
EndModule
;==============================================================
Module = "SIEMENS SITRANS F Beginn" 0x01,0xfc
50
EndModule
Module = "== Free place" 0x00
51
EndModule
Module = "== Flow (short)" 0x94
52
EndModule
Module = "== Flow (long)" 0x42, 0x84, 0x08, 0x05
53
EndModule
Module = "== Sound velocity (short)" 0x94
54
EndModule
Module = "== Sound velocity (long)" 0x42, 0x84, 0x08, 0x05
55
EndModule
Module = "== Quantity net (long)" 0x41, 0x84, 0x85
56
EndModule
Module = "== Resettable quantity net (lg.)" 0xC1, 0x80, 0x84, 0x85
57
EndModule
Module = "== Temperature (short)" 0x94
58
EndModule
Module = "== Temperature (long)" 0x42, 0x84, 0x08, 0x05
59
EndModule
Module = "== Sound amplitude (short)" 0x94
60
EndModule
Module = "== Sound amplitude (long)" 0x42, 0x84, 0x08, 0x05
61
EndModule
Module = "== Quantity forward (long)" 0x41, 0x84, 0x85
62
EndModule
Module = "== Resettable quant. forw. (lg.)" 0xC1, 0x80, 0x84, 0x85
63
EndModule
Module = "== Quantity reverse (long)" 0x41, 0x84, 0x85
64
EndModule
Module = "== Resettable quant. rev. (long)" 0xC1, 0x80, 0x84, 0x85
65
EndModule
Module = "SIEMENS SITRANS F Ende" 0x01,0xfd
66
EndModule
;==============================================================
Module = "SIEMENS SIPAN 32 Beginn" 0x01,0xfc
460
EndModule
Module = "== Conductivity, temp., 7MA2xxx" 0x94, 0x00, 0x94, 0x00, 0xA1
461
EndModule
Module = "== dis. Oxygen, temp., 7MA30xx" 0x94, 0x00, 0x94, 0x00, 0xA1
462
EndModule
Module = "== pH-value, temp., 7MA10xx" 0x94, 0x00, 0x94, 0x00, 0xA1
463
EndModule
Module = "== ORP-value, temp., 7MA10xx" 0x94, 0x00, 0x94, 0x00, 0xA1
464
EndModule
Module = "== pH- +ORP-val., temp., 7MA11xx" 0x94, 0x94, 0x94, 0x00, 0xA1
465
EndModule
Module = "== 2x pH-value, temp., 7MA11xx" 0x94, 0x94, 0x94, 0x00, 0xA1
466
EndModule
Module = "== 2x ORP-value, temp., 7MA11xx" 0x94, 0x94, 0x94, 0x00, 0xA1
467
EndModule
Module = "SIEMENS SIPAN 32 Ende" 0x01,0xfd
468
EndModule
;==============================================================
Module = "SIEMENS OXYMAT / ULTRAMAT Beginn" 0x01,0xfc
470
EndModule
Module = "== ULTRAMAT 6 (1 component)" 0x94, 0x00, 0x00, 0x00, 0xC1, 0x81, 0x81, 0x83
471
EndModule
Module = "== ULTRAMAT 6 (2 components)" 0x94, 0x94, 0x00, 0x00, 0xC1, 0x81, 0x81, 0x83
472
EndModule
Module = "== ULTRAMAT 23 (1 component)" 0x94, 0x00, 0x00, 0x00, 0xC1, 0x81, 0x81, 0x83
473
EndModule
Module = "== ULTRAMAT 23 (2 components)" 0x94, 0x94, 0x00, 0x00, 0xC1, 0x81, 0x81, 0x83
474
EndModule
Module = "== ULTRAMAT 23 (3 components)" 0x94, 0x94, 0x94, 0x00, 0xC1, 0x81, 0x81, 0x83
475
EndModule
Module = "== ULTRAMAT 23 (4 components)" 0x94, 0x94, 0x94, 0x94, 0xC1, 0x81, 0x81, 0x83
476
EndModule
Module = "== OXYMAT 6" 0x94, 0x00, 0x00, 0x00, 0xC1, 0x81, 0x81, 0x83
477
EndModule
Module = "SIEMENS OXYMAT / ULTRAMAT Ende" 0x01,0xfd
478
EndModule
;==============================================================
Module = "SIEMENS SITRANS LR Beginn" 0x01,0xfc
540
EndModule
Module = "== Free place" 0x00
541
EndModule
Module = "== Level (short)" 0x94
542
EndModule
Module = "== Level (long)" 0x42, 0x84, 0x08, 0x05
543
EndModule
Module = "== Volume (short)" 0x94
544
EndModule
Module = "== Volume (long)" 0x42, 0x84, 0x08, 0x05
545
EndModule
Module = "== Mass (short)" 0x94
546
EndModule
Module = "== Mass (long)" 0x42, 0x84, 0x08, 0x05
547
EndModule
Module = "SIEMENS SITRANS LR Ende" 0x01,0xfd
548
EndModule
;==============================================================
Module = "SIEMENS SITRANS FM Beginn" 0x01,0xfc
550
EndModule
Module = "== Free place" 0x00
551
EndModule
Module = "== Flow" 0x94
552
EndModule
Module = "== Quantity net" 0x41, 0x84, 0x85
553
EndModule
Module = "== Resettable quantity net" 0xC1, 0x80, 0x84, 0x85
554
EndModule
Module = "== Quantity forward" 0x41, 0x84, 0x85
555
EndModule
Module = "== Resettable quant. forw." 0xC1, 0x80, 0x84, 0x85
556
EndModule
Module = "== Quantity reverse" 0x41, 0x84, 0x85
557
EndModule
Module = "== Resettable quant. rev." 0xC1, 0x80, 0x84, 0x85
558
EndModule
Module = "SIEMENS SITRANS FM Ende" 0x01,0xfd
559
EndModule
;==============================================================
Module = "SIEMENS SITRANS P DSIII Beginn" 0x01,0xfc
650
EndModule
Module = "== Not in cyclic data transfer" 0x00
651
EndModule
Module = "== Output" 0x94
652
EndModule
Module = "== Counter output" 0x41,0x84,0x85
653
EndModule
Module = "== Counter output with reset" 0xC1,0x80,0x84,0x85
654
EndModule
Module = "== Ctr. output, reset, op. mode" 0xC1,0x81,0x84,0x85
655
EndModule
Module = "SIEMENS SITRANS P DSIII Ende" 0x01,0xfd
656
EndModule
;==============================================================
Module = "E+H Cerabar S PV_Status" 0x42, 0x84, 0x08, 0x05
70
EndModule
;==============================================================
Module = "E+H Cerabar S, 2nd Gener. Beginn" 0x01,0xfc
420
EndModule
Module = "== Main Process Value" 0x42, 0x84, 0x08, 0x05
421
EndModule
Module = "== 2nd Cyclic Value" 0x42, 0x84, 0x08, 0x05
422
EndModule
Module = "== 3rd Cyclic Value" 0x42, 0x84, 0x08, 0x05
423
EndModule
Module = "== Display Value" 0x82, 0x84, 0x08, 0x05
424
EndModule
Module = "== Free Place" 0x00
425
EndModule
Module = "E+H Cerabar S, 2nd Gener. Ende" 0x01,0xfd
426
EndModule
;==============================================================
Module = "E+H Prosonic T PV_Status" 0x42, 0x84, 0x08, 0x05
80
EndModule
;==============================================================
Module = "E+H Prosonic T, 2nd Gen. Beginn" 0x01,0xfc
430
EndModule
Module = "== Main Process Value" 0x42, 0x84, 0x08, 0x05
431
EndModule
Module = "== 2nd Cyclic Value" 0x42, 0x84, 0x08, 0x05
432
EndModule
Module = "== Display Value" 0x82, 0x84, 0x08, 0x05
433
EndModule
Module = "== Free Place" 0x00
434
EndModule
Module = "E+H Prosonic T, 2nd Gener. Ende" 0x01,0xfd
435
EndModule
;==============================================================
Module = "E+H Deltapilot S PV_Status" 0x42, 0x84, 0x08, 0x05
90
EndModule
;==============================================================
Module = "E+H Deltapilot S,2nd Gen. Beginn" 0x01,0xfc
440
EndModule
Module = "== Main Process Value" 0x42, 0x84, 0x08, 0x05
441
EndModule
Module = "== 2nd Cyclic Value" 0x42, 0x84, 0x08, 0x05
442
EndModule
Module = "== Display Value" 0x82, 0x84, 0x08, 0x05
443
EndModule
Module = "== Free Place" 0x00
444
EndModule
Module = "E+H Deltapilot S, 2nd Gen. Ende" 0x01,0xfd
445
EndModule
;==============================================================
Module = "E+H Deltabar S PV_Status" 0x42, 0x84, 0x08, 0x05
100
EndModule
;==============================================================
Module = "E+H Deltabar S, 2nd Gen. Beginn" 0x01,0xfc
450
EndModule
Module = "== Main Process Value" 0x42, 0x84, 0x08, 0x05
451
EndModule
Module = "== 2nd Cyclic Value" 0x42, 0x84, 0x08, 0x05
452
EndModule
Module = "== 3rd Cyclic Value" 0x42, 0x84, 0x08, 0x05
453
EndModule
Module = "== Display Value" 0x82, 0x84, 0x08, 0x05
454
EndModule
Module = "== Free Place" 0x00
455
EndModule
Module = "E+H Deltabar S, 2nd Gener. Ende" 0x01,0xfd
456
EndModule
;==============================================================
Module = "E+H TMD834 PV_Status" 0x42, 0x84, 0x08, 0x05
110
EndModule
;==============================================================
Module = "E+H Micropilot II PV_Status" 0x42, 0x84, 0x08, 0x05
120
EndModule
;==============================================================
Module = "E+H MYCOM CPM Beginn" 0x01,0xfc
130
EndModule
Module = "== Main measurement value" 0x42, 0x84, 0x08, 0x05
131
EndModule
Module = "== Temperature value" 0x42, 0x84, 0x08, 0x05
132
EndModule
Module = "E+H MYCOM CPM Ende" 0x01,0xfd
133
EndModule
;==============================================================
Module = "E+H MYCOM CLM-ID Beginn" 0x01,0xfc
140
EndModule
Module = "== Main measurement value" 0x42, 0x84, 0x08, 0x05
141
EndModule
Module = "== Temperature value" 0x42, 0x84, 0x08, 0x05
142
EndModule
Module = "E+H MYCOM CLM-ID Ende" 0x01,0xfd
143
EndModule
;==============================================================
Module = "E+H MYCOM CLM-CD Beginn" 0x01,0xfc
150
EndModule
Module = "== Main measurement value" 0x42, 0x84, 0x08, 0x05
151
EndModule
Module = "== Temperature value" 0x42, 0x84, 0x08, 0x05
152
EndModule
Module = "E+H MYCOM CLM-CD Ende" 0x01,0xfd
153
EndModule
;==============================================================
Module = "E+H Promag 33,35 Beginn" 0x01,0xfc
160
EndModule
Module = "== Flow Rate Block" 0x42, 0x84, 0x08, 0x05
161
EndModule
Module = "== Total Volume Block" 0x42, 0x84, 0x08, 0x05
162
EndModule