% parameters of SET3C.M

Perunit = 1 % parameters given in per unit of machine base

Frated = 60;
Poles = 2;
Pfrated= 0.9;
Vrated =26e3; 
Prated=722.222e6;
rs = 0.004; % estimate
xd = 1.92;
xq = 1.85;
xls = 0.19;
xpd = 0.34;
xpq = 0.60;
xppd = 0.26;
xppq = 0.26;
Tpdo = 4.8;
Tpqo = 1.0;
Tppdo = 0.04;
Tppqo = 0.053;
H = 3.; % estimate
Domega = 0; % mechanical damping coeff