% Two Area Test Case
%
% bus data format
% bus:
% col1 number
% col2 voltage magnitude(pu)
% col3 voltage angle(degree)
% col4 p_gen(pu)
% col5 q_gen(pu),
% col6 p_load(pu)
% col7 q_load(pu)
% col8 G shunt(pu)
% col9 B shunt(pu)
% col10 bus_type
% bus_type - 1, swing bus
% - 2, generator bus (PV bus)
% - 3, load bus (PQ bus)
% col11 q_gen_max(pu)
% col12 q_gen_min(pu)
% col13 v_rated (kV)
% col14 v_max pu
% col15 v_min pu
bus = [ 1 1.03 18.5 7.00 1.61 0.00 0.00 0.00 0.00 1 99.0 -99.0 22.0 1.1 .9;
2 1.01 8.80 7.00 1.76 0.00 0.00 0.00 0.00 2 5.0 -2.0 22.0 1.1 .9;
3 0.9781 -6.1 0.00 0.00 0.00 0.00 0.00 0.00 3 0.0 0.0 500.0 1.5 .5;
4 0.95 -10 0.00 0.00 9.76 1.00 0.00 0.00 3 0.0 0.0 115.0 1.05 .95;
10 1.0103 12.1 0.00 0.00 0.00 0.00 0.00 0.00 3 0.0 0.0 230.0 1.5 .5;
11 1.03 -6.8 7.16 1.49 0.00 0.00 0.00 0.00 2 5.0 -2.0 22.0 1.1 .9;
12 1.01 -16.9 7.00 1.39 0.00 0.00 0.00 0.00 2 5.0 -2.0 22.0 1.1 .9;
13 0.9899 -31.8 0.00 0.00 0.00 0.00 0.00 0.00 3 0.0 0.0 500.0 1.5 .5;
14 0.95 -38 0.00 0.00 17.67 1.00 0.00 0.00 3 0.0 0.0 115.0 1.05 .95;
20 0.9876 2.1 0.00 0.00 0.00 0.00 0.00 0.00 3 0.0 0.0 230.0 1.5 .5;
101 1.05 -19.3 0.00 8.00 0.00 0.00 0.00 0.00 2 99.0 -99.0 500.0 1.5 .5;
110 1.0125 -13.4 0.00 0.00 0.00 0.00 0.00 0.00 3 0.0 0.0 230.0 1.5 .5;
120 0.9938 -23.6 0.00 0.00 0.00 0.00 0.00 0.00 3 0.0 0.0 230.0 1.5 .5 ];
% line data format
% line: from bus, to bus, resistance(pu), reactance(pu),
% line charging(pu), tap ratio, tap phase, tapmax, tapmin, tapsize
line = [...
1 10 0.0 0.0167 0.00 1.0 0. 0. 0. 0.;
2 20 0.0 0.0167 0.00 1.0 0. 0. 0. 0.;
3 4 0.0 0.005 0.00 1.0 0. 1.2 0.8 0.05;
3 20 0.001 0.0100 0.0175 1.0 0. 0. 0. 0.;
3 101 0.011 0.110 0.1925 1.0 0. 0. 0. 0.;
3 101 0.011 0.110 0.1925 1.0 0. 0. 0. 0.;
10 20 0.0025 0.025 0.0437 1.0 0. 0. 0. 0.;
11 110 0.0 0.0167 0.0 1.0 0. 0. 0. 0.;
12 120 0.0 0.0167 0.0 1.0 0. 0. 0. 0.;
13 14 0.0 0.005 0.00 1.0 0. 1.2 0.8 0.05;
13 101 0.011 0.11 0.1925 1.0 0. 0. 0. 0.;
13 101 0.011 0.11 0.1925 1.0 0. 0. 0. 0.;
13 120 0.001 0.01 0.0175 1.0 0. 0. 0. 0.;
110 120 0.0025 0.025 0.0437 1.0 0. 0. 0. 0.];
% Machine data format
% Machine data format
% 1. machine number,
% 2. bus number,
% 3. base mva,
% 4. leakage reactance x_l(pu),
% 5. resistance r_a(pu),
% 6. d-axis sychronous reactance x_d(pu),
% 7. d-axis transient reactance x'_d(pu),
% 8. d-axis subtransient reactance x"_d(pu),
% 9. d-axis open-circuit time constant T'_do(sec),
% 10. d-axis open-circuit subtransient time constant
% T"_do(sec),
% 11. q-axis sychronous reactance x_q(pu),
% 12. q-axis transient reactance x'_q(pu),
% 13. q-axis subtransient reactance x"_q(pu),
% 14. q-axis open-circuit time constant T'_qo(sec),
% 15. q-axis open circuit subtransient time constant
% T"_qo(sec),
% 16. inertia constant H(sec),
% 17. damping coefficient d_o(pu),
% 18. dampling coefficient d_1(pu),
% 19. bus number
%
% note: all the following machines use sub-transient model
mac_con = [ ...
1 1 900 0.200 0.0025 1.8 0.30 0.25 8.00 0.03...
1.7 0.55 0.25 0.4 0.05...
6.5 0 0 1;
2 2 900 0.200 0.0025 1.8 0.30 0.25 8.00 0.03...
1.7 0.55 0.25 0.4 0.05...
6.5 0 0 2;
3 11 900 0.200 0.0025 1.8 0.30 0.25 8.00 0.03...
1.7 0.55 0.25 0.4 0.05...
6.5 0 0 11;
4 12 900 0.200 0.0025 1.8 0.30 0.25 8.00 0.03...
1.7 0.55 0.25 0.4 0.05...
6.5 0 0 12];
exc_con = [...
1 1 0.01 46.0 0.06 0 0 1.0 -0.9...
0.0 0.46 3.1 0.33 2.3 0.1 0.1 1.0 0 0 0;
3 2 0.01 7.04 1.0 6.67 1.0 10.0 -10.0 ...
0.2 -0.2 200.0 4.37 20 4.83 0.09 1.1 8.63 1.0 6.53;
0 3 0.01 200.0 0 0 0 5.0 -5.0...
0 0 0 0 0 0 0 0 0 0 0;
2 4 0.01 300.0 0.01 0 0 4.95 -4.9...
1.0 1.33 3.05 0.279 2.29 0.117 0.1 0.675 0 0 0];
%pss on exciter 2 and 3
pss_con = [...
1 2 300.0 20.0 0.1 0.02 0.1 0.02 0.2 -0.05;
1 3 300.0 20.0 0.06 0.04 0.08 0.04 0.2 -0.05];
% governor model
% tg_con matrix format
%column data unit
% 1 turbine model number (=1)
% 2 machine number
% 3 speed set point wf pu
% 4 steady state gain 1/R pu
% 5 maximum power order Tmax pu on generator base
% 6 servo time constant Ts sec
% 7 governor time constant Tc sec
% 8 transient gain time constant T3 sec
% 9 HP section time constant T4 sec
% 10 reheater time constant T5 sec
tg_con = [...
1 1 1 25.0 1.0 0.1 0.5 0.0 1.25 5.0;
1 2 1 25.0 1.0 0.1 0.5 0.0 1.25 5.0;
1 3 1 25.0 1.0 0.1 0.5 0.0 1.25 5.0;
1 4 1 25.0 1.0 0.1 0.5 0.0 1.25 5.0];
% non-conforming load
% col 1 bus number
% col 2 fraction const active power load
% col 3 fraction const reactive power load
% col 4 fraction const active current load
% col 5 fraction const reactive current load
load_con = [...
4 0 0 .5 0;
14 0 0 .5 0;
101 0 0 0 0];
disp('0.5 constant current load, svc at bus 101')
%svc
% col 1 svc number
% col 2 bus number
% col 3 svc base MVA
% col 4 maximum susceptance Bcvmax(pu)
% col 5 minimum susceptance Bcvmin(pu)
% col 6 regulator gain
% col 7 regulator time constant (s)
svc_con = [1 101 600 1 0 100 0.05];
%Switching file defines the simulation control
% row 1 col1 simulation start time (s) (cols 2 to 6 zeros)
% col7 initial time step (s)
% row 2 col1 fault application time (s)
% col2 bus number at which fault is applied
% col3 bus number defining far end of faulted line
% col4 zero sequence impedance in pu on system base
% col5 negative sequence impedance in pu on system base
% col6 type of fault - 0 three phase
% - 1 line to ground
% - 2 line-to-line to ground
% - 3 line-to-line
% - 4 loss of line with no fault
% - 5 loss of load at bus
% col7 time step for fault period (s)
% row 3 col1 near end fault clearing time (s) (cols 2 to 6 zeros)
% col7 time step for second part of fault (s)
% row 4 col1 far end fault clearing time (s) (cols 2 to 6 zeros)
% col7 time step for fault cleared simulation (s)
% row 5 col1 time to change step length (s)
% col7 time step (s)
%
%
%
% row n col1 finishing time (s) (n indicates that intermediate rows may be inserted)
sw_con = [...
0 0 0 0 0 0 0.005;%sets intitial time step
0.1 3 101 0 0 0 0.0025; %apply three phase fault at bus 3, on line 3-101
0.15 0 0 0 0 0 0.0025; %clear fault at bus 3
0.20 0 0 0 0 0 0.0025; %clear remote end
0.50 0 0 0 0 0 0.005; % increase time step
1.0 0 0 0 0 0 0.01; % increase time step
2.0 0 0 0 0 0 0]; % end simulation