     Load flow solved in    9  iterations

 Contingency CC42
 ====================


   ** Solution diverged after  78 iterations **

 >> Shunt control was not effective. Switching one more block                                                                       


 >> Shunt control was not effective. The last shunt block is switched.                                                              


 >> Adjusting switchable shunts

 Bus #      Bus name     SWS ID    delt-B   Sensit.   B-max     B       B-min                                                       
  1943 B1943 25.2                    1.20    0.330     4.80     1.20     0.00                                                       


 >> Shunt block is small. Switching more blocks                                                                                     


 Bus #      Bus name     SWS ID    delt-B   Sensit.   B-max     B       B-min                                                       
  1943 B1943 25.2                    2.40    0.330     4.80     2.40     0.00                                                       


 >> Checking voltage violations

 Pre-contingency
 ===============

     Load flow solved in    2  iterations

 Contingency CC41
 ====================

     Load flow solved in    8  iterations

 Contingency CC42
 ====================

     Load flow solved in    9  iterations

 Contingency CC81
 ====================

     Load flow solved in    9  iterations

 Contingency CC82
 ====================

     Load flow solved in    9  iterations

 Contingency CC87
 ====================

     Load flow solved in    7  iterations

 Contingency A   4
 ====================

     Load flow solved in    9  iterations

 Contingency A   8
 ====================

     Load flow solved in    9  iterations

 Pre-contingency
 ===============

     Load flow solved in    6  iterations

 Contingency CC41
 ====================

     Load flow solved in    9  iterations

 Contingency CC42
 ====================


   ** Solution diverged after  72 iterations **

 >> Shunt control was not effective. Switching one more block                                                                       


 Bus #      Bus name     SWS ID    delt-B   Sensit.   B-max     B       B-min                                                       
  1943 B1943 25.2                    3.60    0.330     4.80     3.60     0.00                                                       


 >> Checking voltage violations

 Pre-contingency
 ===============

     Load flow solved in    3  iterations

 Contingency CC41
 ====================

     Load flow solved in    8  iterations

 Contingency CC42
 ====================

     Load flow solved in    9  iterations

 Contingency CC81
 ====================

     Load flow solved in    9  iterations

 Contingency CC82
 ====================

     Load flow solved in    9  iterations

 Contingency CC87
 ====================

     Load flow solved in    6  iterations

 Contingency A   4
 ====================

     Load flow solved in    9  iterations

 Contingency A   8
 ====================

     Load flow solved in    9  iterations

 Pre-contingency
 ===============

     Load flow solved in    6  iterations

 Contingency CC41
 ====================

     Load flow solved in    9  iterations

 Contingency CC42
 ====================

     Load flow solved in   49  iterations

 Contingency CC81
 ====================

     Load flow solved in   16  iterations

 Contingency CC82
 ====================

     Load flow solved in   23  iterations

 Contingency CC87
 ====================

     Load flow solved in    7  iterations

 Contingency A   4
 ====================

     Load flow solved in   30  iterations

 Contingency A   8
 ====================

     Load flow solved in   24  iterations

 Stress level:     68.25 %

 Pre-contingency
 ===============

     Load flow solved in    7  iterations

 Contingency CC41
 ====================

     Load flow solved in    9  iterations

 Contingency CC42
 ====================


   ** Solution diverged after  35 iterations **

 >> Switchable shunt control was effective in increasing the stability margin


 >> Computing the sensitivities at Stress level:   63.25 %

 Pre-contingency
 ===============

     Load flow solved in    8  iterations

 Contingency CC42
 ====================

     Load flow solved in   54  iterations

 >> Computing the sensitivities at Stress level:   58.25 %

 Pre-contingency
 ===============

     Load flow solved in    6  iterations

 Contingency CC42
 ====================

     Load flow solved in   17  iterations

 >> Adjusting switchable shunts

 Bus #      Bus name     SWS ID    delt-B   Sensit.   B-max     B       B-min                                                       
  1906 B1906 25.2                    1.80    0.335     3.00     1.80     0.00                                                       


 >> Shunt block is small. Switching more blocks                                                                                     


 Bus #      Bus name     SWS ID    delt-B   Sensit.   B-max     B       B-min                                                       
  1906 B1906 25.2                    3.00    0.335     3.00     3.00     0.00                                                       


 >> Checking voltage violations

 Pre-contingency
 ===============

     Load flow solved in    2  iterations

 Contingency CC41
 ====================

     Load flow solved in    8  iterations

 Contingency CC42
 ====================

     Load flow solved in    9  iterations

 Contingency CC81
 ====================

     Load flow solved in    9  iterations

 Contingency CC82
 ====================

     Load flow solved in    9  iterations

 Contingency CC87
 ====================

     Load flow solved in    6  iterations

 Contingency A   4
 ====================

     Load flow solved in    9  iterations

 Contingency A   8
 ====================

     Load flow solved in    9  iterations

 Pre-contingency
 ===============

     Load flow solved in    7  iterations

 Contingency CC41
 ====================

     Load flow solved in    9  iterations

 Contingency CC42
 ====================


   ** Solution diverged after  38 iterations **

 >> Shunt control was not effective. Switching one more block                                                                       


 >> Shunt control was not effective. The last shunt block is switched.                                                              


 >> Adjusting switchable shunts

 Bus #      Bus name     SWS ID    delt-B   Sensit.   B-max     B       B-min                                                       
  1943 B1943 25.2                    1.20    0.334     4.80     4.80     0.00                                                       


 >> Checking voltage violations

 Pre-contingency
 ===============

     Load flow solved in    2  iterations

 Contingency CC41
 ====================

     Load flow solved in    8  iterations

 Contingency CC42
 ====================

     Load flow solved in    9  iterations

 Contingency CC81
 ====================

     Load flow solved in    9  iterations

 Contingency CC82
 ====================

     Load flow solved in    9  iterations

 Contingency CC87
 ====================

     Load flow solved in    6  iterations

 Contingency A   4
 ====================

     Load flow solved in    9  iterations

 Contingency A   8
 ====================

     Load flow solved in    9  iterations

 Pre-contingency
 ===============

     Load flow solved in    7  iterations

 Contingency CC41
 ====================

     Load flow solved in    9  iterations

 Contingency CC42
 ====================


   ** Solution diverged after  39 iterations **

 >> Shunt control was not effective. Switching one more block                                                                       


 >> Shunt control was not effective. The last shunt block is switched.                                                              


 >> Stability margin is increased to   63.25 %


 >> Controls are not enough to remove post-contingency stability margin violations



 >> Preventive control was not successful for all contingencies
 
 >> Preventive control for pre-contigency case only



 >> Removing pre-contingency stability margin violation


 >> Stress level:   102.00 %

 Pre-contingency
 ===============

     Load flow solved in    9  iterations


 >> Controls succeeded in removing pre-contingency stability margin violation



 >> Removing pre-contingency VAr reserve violations


 Pre-contingency
 ===============

     Load flow solved in    2  iterations


 >> Preventive control is completed for pre-contingency case only
    All pre-contingency violations are removed

                   << Preventive controls >>



 Device     Device ID                          Controlled  Pre-Value   New-Value   Det-Value   Top-limit   Bottom-limit 
            Controlled for
 ---------------------------------------------------------------------------------------------------------------------

 Shunt         1966 B1966 25.2                 Admittance     10.8000     13.2000      2.4000     13.2000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1863 B1863 12.6                 Admittance      1.8000     11.4000      9.6000     11.4000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1959 B1959 25.2                 Admittance      0.0000      3.0000      3.0000      3.0000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1816 B1816 12.6                 Admittance      0.0000     19.2000     19.2000     19.2000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1918 B1918 25.2                 Admittance      0.0000      7.2000      7.2000     12.0000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1918 B1918 25.2                 Admittance      7.2000      9.6000      2.4000     12.0000      0.0000
            CTG:A   4     VS  Margins               

 Shunt         1918 B1918 25.2                 Admittance      9.6000     12.0000      2.4000     12.0000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1915 B1915 25.2                 Admittance      0.0000      5.4000      5.4000      5.4000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1970 B1970 25.2                 Admittance      0.0000      4.8000      4.8000      4.8000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1971 B1971 25.2                 Admittance      0.0000      4.2000      4.2000      4.2000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1839 B1839 12.6                 Admittance      0.0000      8.7000      8.7000      8.7000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1943 B1943 25.2                 Admittance      0.0000      3.6000      3.6000      4.8000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1906 B1906 25.2                 Admittance      0.0000      3.0000      3.0000      3.0000      0.0000
            CTG:CC42      VS  Margins               

 Shunt         1943 B1943 25.2                 Admittance      3.6000      4.8000      1.2000      4.8000      0.0000
            CTG:CC42      VS  Margins               

 


 >> Starting Corrective Control



 >> Corrective control for post-contingency stability


 >> Correcting contingency CC41                                                                                                     


 >> Continuation parameter: -0.00300

 Contingency CC41
 ====================

     Load flow solved in    8  iterations


 >> Control succeeded in solving contingency before stress



 >> Correcting voltage violations


 Pre-contingency
 ===============

     Load flow solved in    2  iterations

 Contingency CC41
 ====================

     Load flow solved in    8  iterations


 >> Controls succeeded in removing voltage violations



 >> Correcting stability margin violation


 >> Stress level:   102.00 %

 Pre-contingency
 ===============

     Load flow solved in    9  iterations

 Contingency CC41
 ====================

     Load flow solved in   13  iterations


 >> Control succeeded in removing stability margin violation



 >> Correcting VAr reserve violations


 Pre-contingency
 ===============

     Load flow solved in    2  iterations

 Contingency CC41
 ====================

     Load flow solved in    8  iterations


 >> Corrective control is completed for this contingency
    All violations of this contingency are removed

                   << Corrective control >>

 Contingency: CC41
 There is no violation


 >> Correcting conti