        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.90546 PHS =    0.00000
  135.734        3  GEN 3   13.8   1    12.06
 SWITCHING ACTION : AT TIME   140.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.89940 PHS =    0.00000
  140.734        3  GEN 3   13.8   1    12.18
 SWITCHING ACTION : AT TIME   145.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.89334 PHS =    0.00000
  145.734        3  GEN 3   13.8   1    12.28
 SWITCHING ACTION : AT TIME   150.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.88728 PHS =    0.00000
  150.734        3  GEN 3   13.8   1    12.37
 SWITCHING ACTION : AT TIME   155.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.88122 PHS =    0.00000
  155.734        3  GEN 3   13.8   1    12.45
 SWITCHING ACTION : AT TIME   160.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.87516 PHS =    0.00000
  160.734        3  GEN 3   13.8   1    12.50
 SWITCHING ACTION : AT TIME   165.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.86910 PHS =    0.00000
  165.734        3  GEN 3   13.8   1    12.53
 SWITCHING ACTION : AT TIME   170.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.86304 PHS =    0.00000
  170.734        3  GEN 3   13.8   1    12.54
 SWITCHING ACTION : AT TIME   175.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.85698 PHS =    0.00000
  175.734        3  GEN 3   13.8   1    12.51
 SWITCHING ACTION : AT TIME   180.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.85092 PHS =    0.00000
  180.734        3  GEN 3   13.8   1    12.45
 SWITCHING ACTION : AT TIME   185.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.84486 PHS =    0.00000
  185.734        3  GEN 3   13.8   1    12.35
 SWITCHING ACTION : AT TIME   190.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.83880 PHS =    0.00000
  190.734        3  GEN 3   13.8   1    12.19
 SWITCHING ACTION : AT TIME   195.734 SECONDS - TRANSFORMER MODIFIED
      FROM BUS :    10 LOAD115.115.
        TO BUS :    11 LOAD13.813.8
           CKT : 1
      R =    0.00000 X =    0.00100 RATIO =    0.83274 PHS =    0.00000
  195.734        3  GEN 3   13.8   1    11.97
 
 
                                            *** SUMMARY OF ULTC OPERATIONS ***
 
                                                 ONR0 - INITIAL TURNS RATIO
                                                 V0   - INITIAL REGULATED BUS VOLTAGE
                                                 T1   - TIME (IN SECOND) OF FIRST TAP OPERATION
                                                 ONR1 - TURNS RATIO AFTER FIRST TAP OPERATION
                                                 V1   - REGULATED BUS VOLTAGE AT FIRST TAPOPERATION
                                                 TL   - TIME (IN SECOND) OF LAST TAP OPERATION
                                                 ONRL - TURNS RATIO AFTER LAST TAP OPERATION
                                                 VL   - REGULATED BUS VOLTAGE AT LAST TAPOPERATION
                                                 NOP  - TOTAL NUMBER OF TAP OPERATIONS
 
          FROM                 TO                     REGULATED
  BUS #   BUS NAME    BUS #   BUS NAME    CT#  BUS #   BUS NAME     ONR0     V0     T1   ONR1     V1     TL   ONRL     VL  NOP
  ----- ------------  ----- ------------  ---  ----- ------------ ------ ------ ------ ------ ------ ------ ------ ------  ---
     10 LOAD115.115.     11 LOAD13.813.8   1      11 LOAD13.813.8  0.954  0.963 41.500  0.948  0.947195.734  0.833  0.779   20
 
 
 
              SYSTEM LOAD SUMMARY TABLE AT THE END OF SIMULATION RUN
              ======================================================
                           TOTAL LOAD  TOTAL SHEDDED LOAD      REMAINING LOAD
                           ----------  ------------------      --------------
                         MW        MX        MW        MX        MW        MX
                  --------- --------- --------- --------- --------- ---------
                    6677.00    999.79      0.00      0.00   6677.00    999.79
 
              SYSTEM GENERATION SUMMARY TABLE AT THE END OF SIMULATION RUN
              ============================================================
                           TOTAL GENERATION  TOTAL SHEDDED GENERATION
                           ----------------  ------------------------
                               MW        MX        MW        MX
                        --------- --------- --------- ---------
                          6222.71   4463.38      0.00      0.00
 
            LOAD SUMMARY TABLE BY AREA AT THE END OF SIMULATION RUN
            =======================================================
   AREA                    TOTAL LOAD  TOTAL SHEDDED LOAD      REMAINING LOAD    TOTAL GENERATION
   ----                    ----------  ------------------      --------------    ----------------
   # NAME                MW        MX        MW        MX        MW        MX        MW        MX
  -- ------------ --------- --------- --------- --------- --------- --------- --------- ---------
   1                   0.00      0.00      0.00      0.00      0.00      0.00   5457.11   3407.79
   2                6677.00    999.79      0.00      0.00   6677.00    999.79    765.61   1055.59

            LOAD SUMMARY TABLE BY ZONE AT THE END OF SIMULATION RUN
            =======================================================
   ZONE                    TOTAL LOAD  TOTAL SHEDDED LOAD      REMAINING LOAD    TOTAL GENERATION
   ----                    ----------  ------------------      --------------    ----------------
   # NAME                MW        MX        MW        MX        MW        MX        MW        MX
  -- ------------ --------- --------- --------- --------- --------- --------- --------- ---------
   1  2 ZONE           0.00      0.00      0.00      0.00      0.00      0.00   5457.11   3407.79
   2  3 ZONE        6677.00    999.79      0.00      0.00   6677.00    999.79    765.61   1055.59

 
                                         ***** BUSES WITH UNACCEPTABLE VOLTAGE DIP *****
  BUS# STATION NAME DURATION                BUS# STATION NAME DURATION                BUS# STATION NAME DURATION              
 ----- ------------ --------------------   ----- ------------ --------------------   ----- ------------ --------------------
    10 LOAD115.115.  158.50
+                                            11 LOAD13.813.8   44.27