📄 example1.csv
字号:
//
// Example Test Script for ModScan Application
//
// Each Script entry consists of the following
// comma delimited data fields:
//
// TEST NAME, NODE, FUNCTION, ADDRESS, LENGTH, DATA, CONTROL CODE
//
// Double slashes on the front of a line denote comments
//
// The following Control Codes may be used (i.e. last field on each line)
// \ -- Continue DATA fields on next line
// C -- Generate Bad CRC message to slave
// D -- Check response data quantity only, (ignore actual data)
// 1 -- Expect Exception Response 01
// 2 -- Expect Exception Response 02
// 4 -- Expect Exception Response 04
// R -- Expect no Response
// T (default) -- Verify Response Data
//
//
// First Test:
// Write 20 Coils to Node 1 starting at address 100
// Data is alternating pattern of ones & zeros
// (DATA field consists of 32-bits and may be specified
// as a decimal, hex or floating-point value)
//
Preset Multiple Coils,1,15,100,20,0xAAAAA,T
//
//
// Second Test:
// Verify results of first test by reading the pattern back
//
Verify Coil Status,1,1,100,20,0xAAAAA,T
//
// Third Test:
// Read 100 Input Status values
// ignore the data and only verify proper quantity returned
//
Verify Input Status,1,2,100,100,0,D
//
//
// Forth Test:
// Check Slave Response to request for 1000 registers
// (Should probably generate an exception response)
//
Test Exception 2,1,3,100,1000,0,2
//
// Fifth Test:
// Check Slave Response to bad CRC
//
Invalid Request,1,1,100,1,0,C
//
// Sixth Test:
// Query an unknown device & expect no response
//
Query Device 73,73,1,1,1,0,R
//
// Seventh Test:
// Write 6 Holding Registers with data
// (Each floating point number represents
// two registers -- The NAME field on the
// continuation line is ignored)
//
Write Floats,1,16,100,6,1.00,\
,2.00,3.00,,,,T
//
// Eighth Test:
// Verify Test Seven by reading back the Registers
//
Read Floats,1,3,100,6,1.00,\
,2.00,3.00,,,,T
//
// END OF SCRIPT
end