📄 caseformat.m
字号:
%CASEFORMAT Defines the MATPOWER case file format.% A MATPOWER case file is an M-file or MAT-file which defines the variables% baseMVA, bus, gen, branch, areas, and gencost. The format of the data is% similar to PTI format except where noted. An item marked with (+) indicates% that it is included in this data but is not part of the PTI format. An item% marked with (-) is one that is in the PTI format but is not included here.%% Bus Data Format% 1 bus number (1 to 29997)% 2 bus type% PQ bus = 1% PV bus = 2% reference bus = 3% isolated bus = 4% 3 Pd, real power demand (MW)% 4 Qd, reactive power demand (MVAr)% 5 Gs, shunt conductance (MW (demanded) at V = 1.0 p.u.)% 6 Bs, shunt susceptance (MVAr (injected) at V = 1.0 p.u.)% 7 area number, 1-100% 8 Vm, voltage magnitude (p.u.)% 9 Va, voltage angle (degrees)% (-) (bus name)% 10 baseKV, base voltage (kV)% 11 zone, loss zone (1-999)% (+) 12 maxVm, maximum voltage magnitude (p.u.)% (+) 13 minVm, minimum voltage magnitude (p.u.)%% Generator Data Format% 1 bus number% (-) (machine identifier, 0-9, A-Z)% 2 Pg, real power output (MW)% 3 Qg, reactive power output (MVAr)% 4 Qmax, maximum reactive power output (MVAr)% 5 Qmin, minimum reactive power output (MVAr)% 6 Vg, voltage magnitude setpoint (p.u.)% (-) (remote controlled bus index)% 7 mBase, total MVA base of this machine, defaults to baseMVA% (-) (machine impedance, p.u. on mBase)% (-) (step up transformer impedance, p.u. on mBase)% (-) (step up transformer off nominal turns ratio)% 8 status, > 0 - machine in service% <= 0 - machine out of service% (-) (% of total VAr's to come from this gen in order to hold V at% remote bus controlled by several generators)% 9 Pmax, maximum real power output (MW)% 10 Pmin, minimum real power output (MW)%% Branch Data Format% 1 f, from bus number% 2 t, to bus number% (-) (circuit identifier)% 3 r, resistance (p.u.)% 4 x, reactance (p.u.)% 5 b, total line charging susceptance (p.u.)% 6 rateA, MVA rating A (long term rating)% 7 rateB, MVA rating B (short term rating)% 8 rateC, MVA rating C (emergency rating)% 9 ratio, transformer off nominal turns ratio ( = 0 for lines )% (taps at 'from' bus, impedance at 'to' bus, i.e. ratio = Vf / Vt)% 10 angle, transformer phase shift angle (degrees)% (-) (Gf, shunt conductance at from bus p.u.)% (-) (Bf, shunt susceptance at from bus p.u.)% (-) (Gt, shunt conductance at to bus p.u.)% (-) (Bt, shunt susceptance at to bus p.u.)% 11 initial branch status, 1 - in service, 0 - out of service%% (+) Area Data Format% 1 i, area number% 2 price_ref_bus, reference bus for that area% % (+) Generator Cost Data Format% NOTE: If gen has n rows, then the first n rows of gencost contain% the cost for active power produced by the corresponding generators.% If gencost has 2*n rows then rows n+1 to 2*n contain the reactive% power costs in the same format.% 1 model, 1 - piecewise linear, 2 - polynomial% 2 startup, startup cost in US dollars% 3 shutdown, shutdown cost in US dollars% 4 n, number of cost coefficients to follow for polynomial% (or data points for piecewise linear) total cost function% 5 and following, cost data, piecewise linear data as:% x0, y0, x1, y1, x2, y2, ...% and polynomial data as, e.g.:% c2, c1, c0% where the polynomial is c0 + c1*P + c2*P^2%% MATPOWER% $Id: caseformat.m,v 1.4 2004/08/23 20:56:01 ray Exp $% by Ray Zimmerman, PSERC Cornell% Copyright (c) 1996-2004 by Power System Engineering Research Center (PSERC)% See http://www.pserc.cornell.edu/matpower/ for more info.
⌨️ 快捷键说明
复制代码
Ctrl + C
搜索代码
Ctrl + F
全屏模式
F11
切换主题
Ctrl + Shift + D
显示快捷键
?
增大字号
Ctrl + =
减小字号
Ctrl + -