upsTestResultsSummary OBJECT-TYPE
SYNTAX INTEGER {
donePass(1),
doneWarning(2),
doneError(3),
aborted(4),
inProgress(5),
noTestsInitiated(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The results of the current or last UPS diagnostics
test performed. The values for donePass(1),
doneWarning(2), and doneError(3) indicate that the
test completed either successfully, with a warning, or
with an error, respectively. The value aborted(4) is
returned for tests which are aborted by setting the
value of upsTestId to upsTestAbortTestInProgress.
Tests which have not yet concluded are indicated by
inProgress(5). The value noTestsInitiated(6)
indicates that no previous test results are available,
such as is the case when no tests have been run since
the last reinitialization of the network management
subsystem and the system has no provision for non-
volatile storage of test results."
::= { upsTest 3 }
upsTestResultsDetail OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
Case [Page 21]
RFC 1628 UPS MIB May 1994
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Additional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returned."
::= { upsTest 4 }
upsTestStartTime OBJECT-TYPE
SYNTAX TimeStamp
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of sysUpTime at the time the test in
progress was initiated, or, if no test is in progress,
the time the previous test was initiated. If the
value of upsTestResultsSummary is noTestsInitiated(6),
upsTestStartTime has the value 0."
::= { upsTest 5 }
upsTestElapsedTime OBJECT-TYPE
SYNTAX TimeInterval
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of time, in TimeTicks, since the test in
progress was initiated, or, if no test is in progress,
the previous test took to complete. If the value of
upsTestResultsSummary is noTestsInitiated(6),
upsTestElapsedTime has the value 0."
::= { upsTest 6 }
--
-- Well known tests.
--
upsWellKnownTests OBJECT IDENTIFIER ::= { upsTest 7 }
upsTestNoTestsInitiated OBJECT-IDENTITY
STATUS current
DESCRIPTION
"No tests have been initiated and no test is in
progress."
::= { upsWellKnownTests 1 }
upsTestAbortTestInProgress OBJECT-IDENTITY
STATUS current
Case [Page 22]
RFC 1628 UPS MIB May 1994
DESCRIPTION
"The test in progress is to be aborted / the test in
progress was aborted."
::= { upsWellKnownTests 2 }
upsTestGeneralSystemsTest OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The manufacturer's standard test of UPS device
systems."
::= { upsWellKnownTests 3 }
upsTestQuickBatteryTest OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A test that is sufficient to determine if the battery
needs replacement."
::= { upsWellKnownTests 4 }
upsTestDeepBatteryCalibration OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is placed on battery to a discharge level,
set by the manufacturer, sufficient to determine
battery replacement and battery run-time with a high
degree of confidence. WARNING: this test will leave
the battery in a low charge state and will require
time for recharging to a level sufficient to provide
normal battery duration for the protected load."
::= { upsWellKnownTests 5 }
--
-- The Control group.
--
upsControl OBJECT IDENTIFIER ::= { upsObjects 8 }
upsShutdownType OBJECT-TYPE
SYNTAX INTEGER {
output(1),
system(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This object determines the nature of the action to be
taken at the time when the countdown of the
Case [Page 23]
RFC 1628 UPS MIB May 1994
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off."
::= { upsControl 1 }
upsShutdownAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indicated number of seconds, or
less if the UPS batteries become depleted. Setting
this object to 0 will cause the shutdown to occur
immediately. Setting this object to -1 will abort the
countdown. If the system is already in the desired
state at the time the countdown reaches 0, then
nothing will happen. That is, there is no additional
action at that time if upsShutdownType = system and
the system is already off. Similarly, there is no
additional action at that time if upsShutdownType =
output and the output is already off. When read,
upsShutdownAfterDelay will return the number of
seconds remaining until shutdown, or -1 if no shutdown
countdown is in effect. On some systems, if the agent
is restarted while a shutdown countdown is in effect,
the countdown may be aborted. Sets to this object
override any upsShutdownAfterDelay already in effect."
::= { upsControl 2 }
upsStartupAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483648)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occur immediately. Setting this
Case [Page 24]
RFC 1628 UPS MIB May 1994
object to -1 will abort the countdown. If the output
is already on at the time the countdown reaches 0,
then nothing will happen. Sets to this object
override the effect of any upsStartupAfterDelay
countdown or upsRebootWithDuration countdown in
progress. When read, upsStartupAfterDelay will return
the number of seconds until startup, or -1 if no
startup countdown is in effect. If the countdown
expires during a utility failure, the startup shall
not occur until the utility power is restored. On
some systems, if the agent is restarted while a
startup countdown is in effect, the countdown is
aborted."
::= { upsControl 3 }
upsRebootWithDuration OBJECT-TYPE
SYNTAX INTEGER (-1..300)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored."
::= { upsControl 4 }
upsAutoRestart OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
Case [Page 25]
RFC 1628 UPS MIB May 1994
"Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an internal battery depleted
condition. Setting this object to 'off' will prevent
the UPS system from restarting after a shutdown until
an operator manually or remotely explicitly restarts
it. If the UPS is in a startup or reboot countdown,
then the UPS will not restart until that delay has
been satisfied."
::= { upsControl 5 }
--
-- The Configuration group.
--
upsConfig OBJECT IDENTIFIER ::= { upsObjects 9 }
upsConfigInputVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The magnitude of the nominal input voltage. On those
systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2."
::= { upsConfig 1 }
upsConfigInputFreq OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2."
::= { upsConfig 2 }
Case [Page 26]
RFC 1628 UPS MIB May 1994
upsConfigOutputVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2."
::= { upsConfig 3 }
upsConfigOutputFreq OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2."
::= { upsConfig 4 }
upsConfigOutputVA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Volt-Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the nominal Volt-Amp rating."
::= { upsConfig 5 }
upsConfigOutputPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the nominal true power rating."
::= { upsConfig 6 }
upsConfigLowBattTime OBJECT-TYPE
Case [Page 27]
RFC 1628 UPS MIB May 1994
SYNTAX NonNegativeInteger
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of upsEstimatedMinutesRemaining at which a